FWE Thermostatic Expansion Valve

Fujikoki F series · Flare

Type FWE Thermostatic Expansion Valve

Has flare connection and can be used for hot gas defrost cycle as well. Evaporating temperature can be set according to the intended use.

Fujikoki FWE thermostatic expansion valve

Overview

This expansion valve can be used over a wide range of applications including cooling, air conditioning, refrigeration, freezing, and ecological equipment. It is also suitable for hot gas defrost cycle.

Capacity
0.35–17.6 kW (nominal)
Pipe sizes
6.35 (1/4) × 12.70 (1/2) mm (in)
9.52 (3/8) × 12.70 (1/2) mm (in)
12.70 (1/2) × 15.88 (5/8) mm (in)
Equalization
Internal or external pressure equalization (E)
Refrigerants
R134a, R407C, R404A, R410A
Also supported
R448A, R449A, R407H, R463A-J
additionally supportable refrigerants listed in the current Fujikoki product lineup
Connection
Flare

FWE model list

Internal eq.External eq.kWPipe in × out
mm (in)
R134aR407CR404AR410AABQuote
FWE-124□□FWE-E124□□0.356.35 (1/4) × 12.70 (1/2)–※––4548Quote
FWE-224□□FWE-E224□□0.7–※––Quote
FWE-324□□FWE-E324□□1.1○○○–Quote
FWE-524□□FWE-E524□□1.8○○○※Quote
FWE-1024□□FWE-E1024□□3.5○○○※Quote
FWE-1524□□FWE-E1524□□5.3○○○※Quote
FWE-134□□FWE-E134□□0.359.52 (3/8) × 12.70 (1/2)–※––4547Quote
FWE-234□□FWE-E234□□0.7–※––Quote
FWE-334□□FWE-E334□□1.1○○○–Quote
FWE-534□□FWE-E534□□1.8○○○○Quote
FWE-1034□□FWE-E1034□□3.5○○○○Quote
FWE-1534□□FWE-E1534□□5.3○○○○Quote
FWE-2034□□FWE-E2034□□7.0○○○○Quote
FWE-2534□□FWE-E2534□□8.8○○○○Quote
FWE-3034□□FWE-E3034□□10.6○○○○Quote
FWE-4034□□FWE-E4034□□14.1–○–○Quote
FWE-5034□□FWE-E5034□□17.6–○––Quote
FWE-2045□□FWE-E2045□□7.012.70 (1/2) × 15.88 (5/8)○–○–4749Quote
FWE-2545□□FWE-E2545□□8.8○–○–Quote
FWE-3045□□FWE-E3045□□10.6○○○–Quote
FWE-4045□□FWE-E4045□□14.1–○––Quote
FWE-5045□□FWE-E5045□□17.6–○––Quote
○Listed in the catalog※Build-to-order–Not listed for this refrigerant□□ = refrigerant code + evaporating temperature code (see below)Dimensions in mm

Specifications

Adjustment range of static superheat1°C to 7°C (usually, adjustment is unnecessary — do not spin the adjusting nut)
Factory default settingStatic superheat: 3.5°C to 4.5°C
Maximum working pressureR134a / R407C / R404A: 1.47 MPaG — R410A: 3.3 MPaG
Airtightness pressureR134a / R407C / R404A: 1.67 MPaG — R410A: 3.4 MPaG
Withstand pressureR134a / R407C / R404A: 4.42 MPaG — R410A: 4.5 MPaG
Charge systemGas cross charge
Maximum ambient temperature120°C
ConnectionFlare
Weight330 g (internal pressure equalization), 340 g (external pressure equalization)
Capillary / thermal sensing bulbø2.4 × 1000 mm / ø12.7 × 90 mm

Evaporating temperature range

RefrigerantWide (W)Medium temperature (M)Low temperature (L)
R134a10°C to -30°C-1°C to -30°C-18°C to -30°C
R407C10°C to -40°C-1°C to -40°C-18°C to -40°C
R404A10°C to -45°C-1°C to -45°C-18°C to -45°C
R410A10°C to -45°C——

Dimensions

FWE dimension drawing
Dimensions A, B for each model are in the model list above (mm).

Drip-proof cover for type FWE

Drip-proof cover for FWE

Fasten the covers from both sides with tape. Wrapping with coal tape may provide more enhanced sealing performance. Material: polyethylene foam.

FWE valve list (PDF) →

How to read the model number

Models of the F series are displayed as shown below (example: FWE-E1534QW).

FWEType
EExternal equalization
15Capacity
34Pipe code
QRefrigerant
WEvap. range
Equalizing systemE is appended for external equalization.
Refrigerant codeR134a: Q · R22/R407C: H · R404A: N · R410A: G
Evaporating temperature rangeWide use: W · Medium temperature use: M · Low temperature use: L
Capacity & pipe codeRead them from the model list (for example “1534” = 5.3 kW, 9.52 × 12.70 mm).

Notes

  • Do not allow pressure higher than the airtightness pressure to be applied to the expansion valve when checking the airtightness of the piping.
  • When using the R410A-compatible valve in a heat pump circuit, install the thermal sensing bulb and external equalizing tube between the 4-way valve and the accumulator (at the inlet side of the compressor).
  • The R407C-compatible valve is designed on the basis of an R22-compatible obsolete model, so its values may differ slightly from those listed.
  • For mounting the thermal sensing bulb, see installation tips.

Specifications: FUJIKOKI Product Catalog (2016), page 7; additional refrigerants: Fujikoki product lineup (fujikoki.co.jp).

Need a quote for FWE?

Send the model number (or capacity, refrigerant and pipe size) and the quantity.

Request a Quote